Item |
240-56062765 |
Description |
Schedule A |
Schedule B |
Sub clause |
|
3 |
General requirements |
|
|
1 |
3.2 |
Service conditions (if non-standard) |
|
|
|
|
a) ambient air temperature (average) °C |
-10 to +40 |
-10 to +40 |
|
|
b) altitude m |
1800 |
1800 |
|
|
c) average humidity % |
95 |
95 |
|
|
d) wind pressure Pa |
700 |
700 |
|
|
e) level of pollution: Extra heavy - creepage distance mm mm |
Extra heavy |
Extra heavy |
|
|
arcing distances mm |
Extra heavy |
Extra heavy |
2 |
4 |
Ratings |
|
|
|
|
a) indoor or outdoor use |
Outdoor |
Outdoor |
|
|
b) nominal r.m.s system voltage(Un) kV |
110 |
110 |
|
|
c) maximum r.m.s system voltage(Um) kV |
123 |
123 |
|
|
d) number of phases |
3 |
3 |
|
|
e) frequency Hz |
50 |
50 |
|
|
f) method of earthing: effective or non-effective |
effective |
effective |
|
|
g) single-phase or 3-phase voltage transformer? |
single-phase |
single-phase |
|
|
h) Short-time power frequency withstand level kV |
275 |
230 |
|
|
i) lightning impulse withstand level (LIWL) kV |
650 |
550 |
|
|
|
|
|
3 |
|
Manufacturing details |
|
|
|
|
a) manufacturer |
xxxxxxxx |
|
|
|
b) manufacturer's type designation |
xxxxxxxx |
JDCF-110W3 |
|
|
|
|
|
4 |
5.5 |
Requirements for external insulation |
|
|
|
|
Manufacturer of HV porcelain insulators |
xxxxxxxx |
|
|
|
Manufacturer of HV composite insulators |
xxxxxxxx |
NA |
|
10.1.3 |
Detailed drawing of insulator |
Yes |
Yes |
|
|
Compliance with Specification: IEC 60815. |
Yes |
Yes |
|
|
Insulation medium (gas,oil,resin) |
Oil |
Oil |
|
|
|
|
|
5 |
5.1 |
Details of oil-paper insulated voltage
transformers |
|
|
|
|
Type of oil |
xxxxxxxx |
|
|
|
Oil to be certified to contain no PCBs (zero count) |
Yes |
Yes |
|
|
Quantity of oil required litres |
xxxxxxxx |
175kg |
|
|
Expansion accommodation method |
xxxxxxxx |
Bellows |
|
|
Details of sealing arrangements |
xxxxxxxx |
Attach drawing |
|
|
Oil-level indicators |
Yes |
Yes |
|
|
Oil sample valve required? |
No |
No |
6 |
|
Design details |
|
|
|
|
Voltage factor |
minimum 1.9 |
1.2continuous |
|
|
Time for voltage factor s |
minimum 8Hrs |
1.5,30s |
|
|
Primary voltage kV |
110 |
110 |
|
|
Secondary voltage V |
110/Ö3 |
110/Ö3 |
|
|
Measuring or protection application: |
both |
both |
|
|
Rated burden per phase |
100 |
NA |
|
|
1. Rated burden per phase: Distribution unit (Table 1) VA |
100 |
50/50 |
|
4.7.3 |
Accuracy class |
table on pg 1 |
table on pg 1 |
|
|
HV neutral to be earthed? |
Yes |
Yes |
|
|
Is a power winding required? |
No |
No |
|
|
Short-circuit protection |
Yes |
Yes |
|
|
Are primary fuses required? |
No |
No |
|
|
Protection of secondary winding required |
Yes |
Yes |
|
|
a) by means of fuses/MCB's? |
xxxxxxxx |
MCB |
|
|
b) current rating A |
xxxxxxxx |
16 |
|
|
c) make and type of protection |
xxxxxxxx |
MCB |
|
|
d) white phase or neutral to be earthed |
Neutral |
Neutral |
|
|
Short-circuit currents |
|
|
|
|
a) calculated secondary short-circuit current A |
xxxxxxxx |
900 |
|
|
b) maximum permissible duration of secondary short-circuit curr s |
1 |
1 |
|
|
c) operating time for secondary short-circuit s |
xxxxxxxx |
1 |
|
|
d) calculated primary current for a secondary short-circuit assuming zero source impedance A |
xxxxxxxx |
0.75 |
|
|
e) drawing showing method of mounting secondary fuses/MCB's |
xxxxxxxx |
Attach drawing |
|
|
Number of core limbs: |
xxxxxxxx |
2 |
|
|
|
|
|
7 |
6 |
Constructional requirements |
xxxxxxxx |
|
|
|
Windings and connections |
|
|
|
|
Is a residual voltage winding required? |
No |
No |
|
|
Are tapped windings for providing both rated secondary residual voltages required? |
No |
No |
|
|
Details of primary winding neutral (earth) terminal |
Yes |
Yes |
|
|
|
|
|
8 |
6.3 |
Secondary terminal box |
|
|
|
|
Number of fuses/MCB's |
xxxxxxxx |
2 |
|
|
Manufacturer of fuses/MCB's |
xxxxxxxx |
TBA |
|
|
Type of fuses/MCB's |
xxxxxxxx |
16A |
|
|
Current rating of fuses/MCB's A |
xxxxxxxx |
16 |
|
|
MCB Characteristic curve (Curve C) |
xxxxxxxx |
Yes |
|
|
If MCB is used change-over auxiliary contact required |
Yes |
Yes |
|
|
HV winding earth end to be brought out, with link to earth terminal |
Yes |
Yes |
|
|
Dimension of terminal box: |
|
|
|
|
a) length mm |
xxxxxxxx |
298 |
|
|
b) height mm |
xxxxxxxx |
230 |
|
|
c) depth mm |
xxxxxxxx |
208 |
|
|
Minimum effective gland area of secondary terminal box/gland plate; length x width mm |
75 x 50 |
75 x 50 |
|
|
Bolted link or removable link? |
removable |
Bolted link |
|
6.2 |
Secondary terminals (Stud Type size M6) |
Yes |
Phoenix terminal |
9 |
6.6 |
Mounting arrangement |
|
|
|
|
Outline drawing |
Yes |
Yes |
|
|
Holding down bolts to be arranged to fall within a square of maximum dimensions mm |
706 |
706 |
|
|
|
|
|
10 |
6.7 |
Metal finish |
|
|
|
|
Is metal spraying of ferrous parts acceptable? |
Yes |
Yes |
|
|
Finish offered on ferrous parts |
xxxxxxxx |
+ |
|
|
Finish offered on non-ferrous parts |
xxxxxxxx |
NA |
|
|
|
|
|
11 |
6.1 |
Primary terminals |
|
|
|
|
1. Materials: |
xxxxxxxx |
Aluminium |
|
|
2. Type of primary terminal |
Stem |
Stem |
|
|
Dimensions and orientation of stem: |
|
|
|
|
a) diameter mm |
26 |
26 |
|
|
b) minimum length mm |
125 |
125 |
|
|
c) orientation |
Vertical |
Horizontal |
|
|
Details of earthing terminal suitable for 50x3mm strap |
xxxxxxxx |
Yes |
|
|
|
|
|
12 |
6.9 |
Rating plates and diagram plates |
|
|
|
|
a) materials used for rating plates |
xxxxxxxx |
Stainless steel |
|
|
b) material used for diagram plates |
xxxxxxxx |
In rating plate |
|
|
c) method of fixing diagram plates and rating plates |
xxxxxxxx |
Fastening screw |
|
|
|
|
|
13 |
|
Cores |
|
|
|
|
Core steel details |
|
|
|
|
a) grade |
xxxxxxxx |
35Q |
|
|
b) thickness of lamina mm |
xxxxxxxx |
0.35 |
|
|
a) annealed? |
xxxxxxxx |
Yes |
|
|
b) B/H curve to be supplied |
Yes |
Yes |
|
|
|
|
|
14 |
5.4 & 5.5 |
Drawings and instruction manuals |
|
|
|
|
Quantity of drawings and literature required with tender |
1 |
1 |
|
|
Information in electronic format (PDF etc) |
Yes |
Yes |
|
|
Mass of complete transformer kg |
xxxxxxxx |
735 |
|
|
Number of instruction books and descriptive pamphlets per order |
3 |
3 |
|
|
|
|
|
|
|
Drawing numbers for post-type voltage transformers: |
|
|
|
|
a) outline dimension |
xxxxxxxx |
Yes |
|
|
b) assembly |
xxxxxxxx |
Yes |
|
|
c) terminal box |
xxxxxxxx |
Yes |
|
|
d) terminal marking |
xxxxxxxx |
Yes |
|
|
e) rating plate |
xxxxxxxx |
Yes |
|
|
f) diagram plate |
xxxxxxxx |
Yes |
|
|
|
|
|
|
7.5 |
Test certificates of individual routine tests |
Yes |
Yes |
|
|
are required and shall be placed in the |
|
Yes |
|
|
terminal box |
|
|
|
|
|
|
|
15 |
4.10 |
Spare fuses |
|
|
|
|
Secondary fuses: One spare in terminal box |
Yes |
Yes |
|
|
|
|
|
16 |
7.2 |
Type tests |
|
|
|
|
Temperature Rise Test |
Yes |
Yes |
|
|
Lightning impulse test of primary terminals |
Yes |
Yes |
|
|
Wet Test for Outdoor Transformers |
Yes |
Yes |
|
|
Measument of RIV |
Yes |
Yes |
|
|
Determination of Errors (Accuracy Test) |
Yes |
Yes |
|
|
Short circuit withstand capability test |
Yes |
Yes |
|
|
Verification of degree of protection by enclosure |
Yes |
Yes |
|
|
|
|
|
17 |
7.4 |
Special tests |
|
|
|
|
Chopped impulse voltage withstand test on primary windings |
Yes |
Yes |
|
|
Mechanical tests |
Yes |
Yes |
|
|
Transmitted overvoltage test |
Yes |
Yes |
|
|
Internal arc fault test |
Yes |
NO |
|
|
Corrosion test |
Yes |
NO |